Check an emergency power cut-off (EPO) switch is located near the main IT area entrance. It must be clearly labeled and have a protective cover. This requirement is only for computer centers with large server rooms and/or supporting infrastructure rooms hosting large amounts of network equipment and/or equipment such as chillers, battery backup, transformers, etc. NOTES: In general such an area will be in raised floor space. The requirement should not be applied to purely administrative/office space. Also, this requirement should not be applied to a tactical environment, unless it is clearly an "established" fixed computer facility supporting missions in a Theater of Operations. The standards to be applied to determine applicability in a tactical environment are: 1) The facility containing the computer room has been in operation over 1-year. 2) The facility is "fixed facility" - a hard building made from normal construction materials - wood, steel, brick, stone, mortar, etc. |