A master power switch or emergency cut-off switch to IT equipment is present. It is located near the main entrance of the IT area and it is labeled and protected by a cover to prevent accidental shut-off.
MAC / CONF | Impact | Subject Area |
---|---|---|
MACI MACII MACIII | High | Physical and Environmental |
Threat |
---|
IT assets are at risk to electrical damage if a master power switch is not available or operational at a critical moment. |
Guidance |
---|
1. A master power switch or emergency cut-off switch to IT equipment shall be present in the facility. 2. A master power switch or emergency cut-off switch to IT equipment shall be located near the main entrance of the IT area. 3. A master power switch or emergency cut-off switch to IT equipment shall be protected by a cover to prevent accidental shut-off. 4. Testing of the master power switch or emergency cut-off switch shall be tested in accordance with building code regulations. |