UCF STIG Viewer Logo

Sufficient backup power is not provided for the LAN Infrastructure, WAN boundary, VVoIP infrastructure, and/or VVoIP endpoints as required in support of special-C2 and C2 users system availability needs during a power outage OR sufficient backup power is not provided to C2-R or non-C2/admin user accessible endpoints, minimally in support of emergency life-safety and security calls.


Overview

Finding ID Version Rule ID IA Controls Severity
V-21516 VVoIP 1221 (GENERAL) SV-23726r1_rule Medium
Description
DoD Policy requires special-C2 users to be provided 8 hours of backup power in support of their VVoIP communications needs when primary power has failed. From CJCSI 6215.01C Appendix A Enclosure C Based on the GIG MA ICD requirements associated with availability and reliability, the following requirements shall be met by IP based RTS. (a) Availability requirement for equipment/software serving Special C2 users is 0.99999 with eight hours uninterrupted power supply. As such, all elements of the LAN infrastructure, WAN boundary infrastructure, VVoIP infrastructure, and VVoIP endpoints that directly support any Special-C2 user must be provided with sufficient backup power to meet the availability requirements.
STIG Date
VOICE and VIDEO over INTERNET PROTOCOL (VVoIP) POLICY SECURITY TECHNICAL IMPLEMENTATION GUIDE 2010-08-17

Details

Check Text ( C-25760r1_chk )
Interview the IAO to confirm compliance with the following requirement:

Ensure an uninterruptible power supply (battery at a minimum; plus optional generator) is provided for all parts of the VVoIP infrastructure (Core LSC/MFSS, adjunct systems providing critical services, EBC, CER, LAN NEs, and endpoints as follows:
> All VVoIP system devices including voice endpoints and portions of the LAN that directly support one or more special-C2 users are minimally provided 8 hours UPS.
> UPS systems supplying power to infrastructure that supports special-C2 and C2 users must also support environmental power (for example cooling power) such that equipment failures are prevented. This support may not need to be continuous but must be commensurate with the users supported (8 or 2hrs as appropriate).
UPS.

Fix Text (F-22306r1_fix)
Ensure an uninterruptible power supply (battery at a minimum; plus optional generator) is provided for all parts of the VVoIP infrastructure (Core LSC/MFSS, adjunct systems providing critical services, EBC, CER, LAN NEs, and endpoints as follows:
> All VVoIP system devices including voice endpoints and portions of the LAN that directly support one or more special-C2 user are minimally provided 8 hours UPS.

> UPS systems supplying power to infrastructure that supports special-C2 and C2 users must also support environmental power (for example cooling power) such that equipment failures are prevented. This support may not need to be continuous but must be commensurate with the users supported (8 or 2hrs as appropriate).
UPS

Install, upgrade, and maintain UPS systems as needed to meet the backup power requirements.