TEMPEST - Red/Black Separation (Cables)


Overview

Finding ID Version Rule ID IA Controls Severity
V-245756 EM-03.02.01 SV-245756r822823_rule Medium
Description
Failure to maintain proper separation could result in detectable emanations of classified information. REFERENCES: CJCSI 6510.01F, INFORMATION ASSURANCE (IA) AND SUPPORT TO COMPUTER NETWORK DEFENSE (CND) DoD 5220.22-M (NISPOM), Incorporating Change 2, 18 May 2016, Chapter 11 NIST Special Publication 800-53 (SP 800-53), Rev 4, Controls: PE-19 & PE-19(1) Committee on National Security Systems Policy 300, "National Policy on Control of Compromising Emanations," April 2004, as amended Committee on National Security Systems Instruction 7000, "TEMPEST Countermeasures for Facilities," May 2004, as amended DoDI 8500.01, SUBJECT: Cybersecurity, March 14, 2014 CNSSAM TEMPEST/ 1-13, 17 January 2014, RED/BLACK Installation Guidance
STIG Date
Traditional Security Checklist 2022-09-22

Details

Check Text ( C-49187r769928_chk )
Check that unless separated by a metal distribution system such as conduit or enclosed cable tray, a minimum separation distance of 5 cm (2 inches) or (15 cm (6 inches) for parallel cable lengths over 30 meters (98.4 feet)) is provided between any RED wire line and BLACK wire lines that exit the inspectable space or are connected to an RF transmitter, or BLACK power lines, or a digital switch (such as a computerized telephone switch or network router) that is contained within the inspectable space.

NOTES:

1. This requirement is applicable in a tactical environment.

2. The supporting CTTA should always be contacted for specific separation requirements, which may be greater than the distance reflected in this check.

3. Inspectable Space is the three dimensional space surrounding equipment that processes classified and/or sensitive information within which TEMPEST exploitation is not considered practical or where legal authority to identify and remove a potential TEMPEST exploitation exists and is exercised. CTTAs have the authority to define the inspectable space.
Fix Text (F-49142r769929_fix)
Unless separated by a metal distribution system such as conduit or enclosed cable tray, a minimum separation distance of 5 cm (2 inches) or ( 15 cm (6 inches) for parallel cable lengths over 30 meters (98.4 feet)) shall be provided between any RED wire line and BLACK wire lines that exit the inspectable space or are connected to an RF transmitter, or BLACK power lines, or a digital switch (such as a computerized telephone switch or network router) that is contained within the inspectable space.

NOTES:

1. This requirement is applicable in a tactical environment.

2. The supporting CTTA should always be contacted for specific separation requirements, which may be greater than the distance reflected in this check.

3. Inspectable Space is the three dimensional space surrounding equipment that processes classified and/or sensitive information within which TEMPEST exploitation is not considered practical or where legal authority to identify and remove a potential TEMPEST exploitation exists and is exercised. CTTAs have the authority to define the inspectable space.