Vault/Secure Room Storage Standards - IDS Transmission Line Security


Overview

Finding ID Version Rule ID IA Controls Severity
V-31284 IS-02.01.11 SV-41552r2_rule PEPF-2 PESS-1 High
Description
Failure to meet standards for ensuring integrity of the intrusion detection system signal transmission supporting a secure room (AKA: collateral classified open storage area) containing SIPRNet assets could result in the undetected loss or compromise of classified material.
STIG Date
Traditional Security 2013-07-11

Details

Check Text ( C-40045r5_chk )
Explanation of requirement:

Transmission lines used to carry IDS sensor alarm signals between secure rooms or areas containing SIPRNet assets and IDS monitoring equipment, shall have line supervision.

If all portions of an IDS transmission line (protecting SIPRNet assets) are run within secret or higher secure area space or secret or higher controlled access area (CAA) spaces it will not require line supervision.

Check:

Check that Class I or Class II line supervision is being used IAW DoD Manual 5200.01, with the exception of portions of the transmission line running entirely through spaces or areas where unescorted access is controlled to at least the Secret level.

In summary, if portions of the transmission line run through spaces or areas where unescorted access is not controlled to at least the Secret level - it will require line supervision.

The check and verification of line supervision can be obtained by viewing IDS specifications from the vendor, or by conducting a controlled test of a transmission line/signal.

TACTICAL ENVIRONMENT: This check is applicable where Vaults/Secure Rooms are used to protect classified materials or systems in a tactical environment. The only exception will be for urgent (short term) tactical operations or other contingency situations where fixed facilities and equipment are not yet present or incapable of being used.
Fix Text (F-35201r3_fix)
Explanation of requirement:

Transmission lines used to carry IDS sensor alarm signals between secure rooms or areas containing SIPRNet assets and IDS monitoring equipment, shall have line supervision.

If all portions of an IDS transmission line (protecting SIPRNet assets) are run within secret or higher secure area space or secret or higher controlled access area (CAA) spaces it will not require line supervision.

Fix:

Class I or Class II line supervision must be used IAW DoD Manual 5200.01 for protection of IDS transmission line signals, with the exception of portions of the transmission line running entirely through spaces or areas where unescorted access is controlled to at least the Secret level.

In summary, if portions of the transmission line run through spaces or areas where unescorted access is not controlled to at least the Secret level - it requires line supervision.

Verification of line supervision can be obtained by viewing IDS specifications from the vendor, or by conducting a controlled test of a transmission line/signal.