Finding ID | Version | Rule ID | IA Controls | Severity |
---|---|---|---|---|
V-30942 | CS-04.01.02 | SV-40984r3_rule | DCSR-3 ECCT-2 PESS-1 | High |
Description |
---|
A PDS that is not constructed and configured as required could result in the undetected interception of classified information. |
STIG | Date |
---|---|
Traditional Security | 2013-07-11 |
Check Text ( C-39602r4_chk ) |
---|
Check to ensure data cables are installed in a carrier configured as a "Hardened Carrier". The carrier must be constructed of electrical metallic tubing (EMT), ferrous conduit or pipe, or rigid-sheet steel ducting, utilizing elbows, couplings, nipples, and connectors of the same material. NOTE: A Modular PDS may be used if constructed of solid metal components - as described above. |
Fix Text (F-34756r4_fix) |
---|
Data cables must be installed in a carrier configured as a "Hardened Carrier" IAW NSTISSI 7003. The carrier must be constructed of electrical metallic tubing (EMT), ferrous conduit or pipe, or rigid-sheet steel ducting, utilizing elbows, couplings, nipples, and connectors of the same material. NOTE: A Modular PDS may be used if constructed of solid metal components - as described above. |